0Viewes
Analysis of Grounding Issue in E-House Fabrication
Repository Analytics
Statistic Details
0Downloaded
0Accessed per month
0Countries
Statistic not available yet or restricted.
Loading...
Date
Authors
Cristian Satrianto, Andhika
Journal Title
Journal ISSN
Volume Title
Publisher
Politeknik Negeri Batam
Abstract
Abstract— The grounding system is a critical element in
the fabrication of electrical house (E-house). Defects in
this stage can reduce the reliability of the system,
increase the potential for safety risks to personnel, and
directly affect the quality of the final fabrication. This
study uses a combination of Fishbone Diagrams and 5
Whys analyses to identify and investigate grounding related issues during the fabrication process. The case
study focuses on two major defects: Grounding
resistance not good and Grounding not installed
properly. A systematic analysis successfully identified
the root causes, which were addressed through
corrective actions. These included recalibrating the
torque tools used for grounding bolt tightening and
reinforcing the consistency of the internal inspection
checklist monitoring process. These improvements were
implemented continuously and effectively reduced
grounding defects while improving installation
performance. The structured approach offered by the
Fishbone and 5 Whys methodologies supports the
prioritization of improvement actions and provides clear
technical guidance to minimize grounding-related risks.
This contributes to enhanced overall fabrication quality.
Description
Citation
IEEE